[+] Garansi Resmi 1 Tahun [+] PRODIGI # 0812-1013-999
ICA RN 2100C 2000VA 1800W Online Sinewave Rackmount Capacity : 2000 VA / 1800 W INPUT Rated voltage : 200 / 208 / 220 / 230 / 240Vac Voltage range : 110 ~ 300Vac (depend on load percentage) Frequency range : 40 ~ 70Hz (auto detect) Power factor : ≥0.99 Bypass voltage range : Bypass high voltage point Setting in LCD from 230Vac to 264Vac (Default: 264Vac) Bypass low voltage point Setting in LCD from 170Vac to 220Vac (Default: 170Vac) Generator input : Support OUTPUT Output voltage : 200 / 208 / 220 / 230 / 240Vac Power factor : 0.9 Voltage regulation : ±1% Frequency line mode : 45 ~ 55Hz (for 50Hz) or 55 ~ 65Hz (for 60Hz) Frequency bat. mode : 50 / 60 (±0.01%)Hz Crest factor : 3 : 1 Harmonic distortion (THDv) : ≤3% with linear load; ≤6% with non-linear load Waveform : Pure sinewave Efficiency (AC mode full load) : >89% SYSTEM Transfer time : Utility to Battery: 0ms; Utility to Bypass: <4ms Overload (Line Mode) : Load ≤110%: last 10min; ≤130%: last 1min; ≤150%: last 5S; >150% turn to bypass mode (1 ~ 3kvA) Load ≤110%: last 60min; ≤125%: last 10min; ≤150%: last 1S; >150% turn to bypass mode (6 ~ 10kvA) Short circuit : Hold whole system Overheat : Line mode: Switch to Bypass; Backup Mode: Shutdown UPS immediately Battery low : Alarm and switch off EPO (optional) : Shutdown UPS immediately Audible & visual alarm : Line failure; Battery Low, Overload, System Fault Coomunication interface : USB (or RS232), SNMP card / relay card (optional) ENVIRONMENTAL Operating temperature : 0 ~ 40º C Storage temperature : -25 ~ 55ºC Humidity range : 20 ~ 90% (non-condensing) Altitude : <1500m Noise level : <50dB at 1 meter PHYSICAL Dimension W x H x D (mm) : 440 x 86.5 x 435 (2U)